This heavy duty gas powered valve is suitable for Ammonia, R-12, R-22, and R-502, other refrigerants, certain oils and other fluids approved for use in refrigeration. They are pilot operated semi-steel bodied valves. The valves may be opened by means of the manual opening stem for servicing or in case of electrical power failure. The Type S9A is a pilot operated valve but uses an external source of higher pressure gas to operate the valve, and, therefore requires no minimum pressure drop to open. The external gas pressure for the Type S9A must be at least 0.69 bar (10 psi) above valve internal upstream pressure for positive opening. This valve is normally closed.